SLS-B+C100
SURGE PROTECTION
-
Single-phase protector (1 pole + NPE).
- Offers high protection thanks to the combination of high-resistance gas discharge tubes (GDT) and a high-energy varistor block (MOV), which allows large discharge capacity and low residual voltage.
- Easily replaceable plug-in modules with locking system.
- Base and modules configured for safe installation.
- Easy maintenance thanks to local fault indicator.
SLS-B+C100/1+1
Lightning and transient surge arrester for single-phase 220 V lines (F+N).
Combined type 1 and 2 protector (class B+C), designed for the protection of low voltage lines against lightning discharges and transient surges up to 50kA (10/350) in TT (TNS) networks. Recommended for industrial installations and buildings with external lightning protection systems.
|
Parameters |
|
L-N |
NPE |
|
Nominal voltage |
Un |
230 V AC |
– |
|
Maximum operating voltage |
Uc |
260 V AC |
255 V AC |
|
Peak lightning current value (10/350µs) |
Iimp |
25 kA |
50 kA |
|
Nominal discharge current (8/20µs) |
In |
30 kA |
50 kA |
|
Maximum discharge current (8/20µs) |
Imax |
60 kA |
100 kA |
|
Protection level |
Up |
<1,50 kV |
|
|
Maximum fuse pre-protection |
|
250 A gL/Gg |
|
|
Response time |
tA |
100 ns |
|
|
Min-max connection cross-section, solid conductor |
|
2,5-50 mm2 |
|
|
Min-max connection cross-section, stranded conductor |
|
2,5-35 mm2 |
|
|
Local fault indicator |
|
yes |
no |
|
Mounting |
|
DIN rail |
|
|
Description |
Reference |
No. of Phases |
Protection degree |
Operating temperature range |
|
SLS-B+C100/1+1 |
370213 |
F+N |
IP20 |
from -40 ºC to 80 ºC |
|
SLS-B+C100/220V |
370215 |
– |
IP20 |
from -40 ºC to 80 ºC |
SLS-B+C100/3+1
Lightning and transient surge arrester for three-phase lines (3F+N) 380 V.
Combined type 1 and 2 protector (class B+C), designed for the protection of low voltage lines against lightning discharges and transient surges up to 100kA (10/350) in TT (TNS) networks. Recommended for industrial installations and buildings with external lightning protection systems.
| Parameters | L-N | ||||||
| Nominal voltage | Un | 230 V AC | |||||
| Maximum operating voltage | Uc | 260 V AC | |||||
| Peak lightning current value (10/350µs) | Iimp | 25 kA | |||||
| Nominal discharge current (8/20µs) | In | 30 kA | |||||
| Maximum discharge current (8/20µs) | Imax | 60 kA | |||||
| Protection level | Up | <1,50 kV | |||||
| Maximum fuse pre-protection | 250 A gL/gG | ||||||
| Response time | tA | 100 ns | |||||
| Min-max connection cross-section, solid conductor | 2,5-50 mm2 | ||||||
| Min-max connection cross-section, stranded conductor | 2,5-35 mm2 | ||||||
| Local fault indicator | yes | ||||||
| Mounting | DIN rail | ||||||
| A (mm) | B (mm) | C (mm) | D (mm) | E (mm) |
Weight |
||
| 72 | 90 | 72 | 45 | 48 |
670 |
||
|
– |
– | – | 45 | 48 |
300 |
||
Standards | Tests | Certifications
lEC 61643-11:2011
UNE 21186:2011
EN 61643-11 :2012
NFC 17-102:2011
UNE 61643-11 :2013
UNE EN 60664-1:2008
lEC 62305-1, 2, 3 y 4
RBT